You can use the parameter Chrt sett.Bool in a CFC chart as an input signal with a Boolean value. This
input value can then be changed during the runtime of the CFC chart.
Parameter: Chart setting Int
•
Default setting Chart setting Int = 10
You can use the parameter Chart setting Int in a CFC chart as an input signal with an integer value.
This input value can then be changed during the runtime of the CFC chart.
Parameter: Chrt sett.real
•
Default setting Chrt sett.real = 100.000
You can use the parameter Chrt sett.real in a CFC chart as an input signal with a floating-point number.
This input value can then be changed during the runtime of the CFC chart.
Settings
Addr. Parameter C Setting Options Default Setting
Chrt sett.Bool
_:105 Chrt sett.Bool:Value
•
0
•
1
false
Addr. Parameter C Setting Options Default Setting
Chart setting Int
_:105 Chart setting Int:Value -2147483648 to 2147483647 10
Addr. Parameter C Setting Options Default Setting
Chrt sett.real
_:105 Chrt sett.real:Value -10000000000.000 % to
10000000000.000 %
100.000 %
Information List
No.
Information Data Class
(Type)
Type
Chrt sett.Bool
_:305 Chrt sett.Bool:Setting value SPS O
No. Information Data Class
(Type)
Type
Chart setting Int
_:305 Chart setting Int:Setting value INS O
No. Information Data Class
(Type)
Type
Chrt sett.real
_:305 Chrt sett.real:Setting value MV O
6.7.4
6.7.5
Control Functions
6.7 CFC-Chart Settings
436 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017