Addr. Parameter C Setting Options Default Setting
_:1981:101 Definite-T 1:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:1981:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 1.50 s
Definite-T 2
_:1982:1 Definite-T 2:Mode
•
off
•
on
•
test
off
_:1982:2 Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:1982:3 Definite-T 2:Threshold 5.0 % to 999.9 % 65.0 %
_:1982:4 Definite-T 2:Dropout
ratio
0.40 to 0.99 0.95
_:1982:104 Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:1982:101 Definite-T 2:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:1982:6 Definite-T 2:Operate
delay
0.00 s to 60.00 s 0.50 s
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:301 General:Overcurrent blocking SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:1981:81 Definite-T 1:>Block stage SPS I
_:1981:52 Definite-T 1:Behavior ENS O
_:1981:53 Definite-T 1:Health ENS O
_:1981:54 Definite-T 1:Inactive SPS O
_:1981:56 Definite-T 1:Operate delay expired ACT O
_:1981:300 Definite-T 1:Inrush blocks operate ACT O
_:1981:55 Definite-T 1:Pickup ACD O
_:1981:57 Definite-T 1:Operate ACT O
Definite-T 2
_:1982:81 Definite-T 2:>Block stage SPS I
_:1982:52 Definite-T 2:Behavior ENS O
_:1982:53 Definite-T 2:Health ENS O
_:1982:54 Definite-T 2:Inactive SPS O
_:1982:56 Definite-T 2:Operate delay expired ACT O
_:1982:300 Definite-T 2:Inrush blocks operate ACT O
_:1982:55 Definite-T 2:Pickup ACD O
_:1982:57 Definite-T 2:Operate ACT O
7.25.6
Protection and Automation Functions
7.25 Negative-Sequence Protection
874 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017