Addr. Parameter C Setting Options Default Setting
Dyn.set: bin.input
_:752:34 Definite-T 2:Effected by
binary input
no
yes
no
_:752:41 Definite-T 2:Stage
blocked
no
yes
no
_:752:19 Definite-T 2:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:752:25 Definite-T 2:Operate
delay
0.00 s to 60.00 s 0.30 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:500 General:>Activation emg. mode SPS I
_:2311:300 General:Emergency mode act. SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:751:81 Definite-T 1:>Block stage SPS I
_:751:84 Definite-T 1:>Activ. dyn. settings SPS I
_:751:500 Definite-T 1:>Block delay & op. SPS I
_:751:54 Definite-T 1:Inactive SPS O
_:751:52 Definite-T 1:Behavior ENS O
_:751:53 Definite-T 1:Health ENS O
_:751:60 Definite-T 1:Inrush blocks operate ACT O
_:751:62 Definite-T 1:Dyn.set. AR cycle1act. SPS O
_:751:63 Definite-T 1:Dyn.set. AR cycle2act. SPS O
_:751:64 Definite-T 1:Dyn.set. AR cycle3act. SPS O
_:751:65 Definite-T 1:Dyn.set. ARcycl.>3act SPS O
_:751:66 Definite-T 1:Dyn.set. CLP active SPS O
_:751:67 Definite-T 1:Dyn.set. BI active SPS O
_:751:68 Definite-T 1:Dyn. set. blks. pickup SPS O
_:751:55 Definite-T 1:Pickup ACD O
_:751:56 Definite-T 1:Operate delay expired ACT O
_:751:57 Definite-T 1:Operate ACT O
7.5.4.4
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 647
C53000-G5040-C015-9, Edition 11.2017