EasyManua.ls Logo

Siemens 6MD86 - Circuit-Breaker Wear Monitoring; Overview of Functions; Structure of the Function

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Circuit-Breaker Wear Monitoring
Overview of Functions
The Circuit-breaker wear monitoring function:
Records the wear of circuit breakers
Allows maintenance intervals of the CB poles to be carried out when their actual degree of wear makes it
necessary
Sends a warning signal when the wear of a circuit breaker reaches a specified degree
Allows the supervision of the circuit-breaker make time
Savings on maintenance and servicing costs is one of the main benefits this functionality offers.
Structure of the Function
The Circuit-breaker wear monitoring function can be used in the Circuit-breaker function group.
The function offers 4 independent operating stages with different measuring methods:
ΣI
x
-method stage
Sum of tripping current powers
2P-method stage
2 points method for calculating the remaining switching cycles
I
2
t-method stage
Sum of all squared fault-current integrals
Supv.CB make time stage
Supervision of the circuit-breaker make time
The function is preconfigured by the manufacturer with 1 ΣI
x
-method stage. A maximum of 1 ΣI
x
-method
stage, 1 2P-method stage, 1 I
2
t-method stage, and 1 Supv.CB make time stage can be operated simultane-
ously within this function.
The general functionality is available across stages and provides a uniform start criterion for the stages.
[DwCBWear, 2, en_US]
Figure 9-21 Structure/Embedding of the Function
9.6
9.6.1
9.6.2
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
1020 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals