Parameter: Temperature unit
To change the display and evaluation of measured temperature values from °C to °F, adapt the DIGSI user
default settings accordingly.
Proceed as follows:
In DIGSI select the menu item Extras --> Settings.
In the Settings view select the menu item DIGSI 5 User preferences.
Under Standard unit system change the setting value of the unit system used from
SI units
to
US
units
.
[scfahrht-190214-01, 1, en_US]
Figure 5-80 Change of the Display Between °C and °F
The following settings and information table shows only 1 of the 12 sensors, as the setting possibilities of the
12 sensors do not differ.
Settings
Addr.
Parameter C Setting Options Default Setting
General
_:2311:103 General:Port
port E
port F
port J
port N
port P
port J
Sensor 1
_:11611:102 Sensor 1:Sensor type
Pt 100
Ni 100
Ni 120
Pt 100
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:53 General:Health ENS O
_:2311:56 General:Failure SPS O
5.7.7.7
5.7.7.8
Function-Group Types
5.7 Function-Group Type Analog Units
282 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017