Addr. Parameter C Setting Options Default Setting
_:101 Inverse-T #:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:102 Inverse-T #:Pickup delay
•
no
•
yes
no
_:3 Inverse-T #:Threshold 0.300 V to 175.000 V 80.000 V
_:109 Inverse-T #:Pickup factor 0.80 to 1.00 0.90
_:103 Inverse-T #:Charact.
constant k
0.00 to 300.00 1.00
_:104 Inverse-T #:Charact.
constant α
0.010 to 5.000 1.000
_:105 Inverse-T #:Charact.
constant c
0.000 to 5.000 0.000
_:106 Inverse-T #:Time dial 0.05 to 15.00 1.00
_:107 Inverse-T #:Additional
time delay
0.00 s to 60.00 s 0.00 s
_:108 Inverse-T #:Reset time 0.00 s to 60.00 s 0.00 s
Information List
No. Information Data Class
(Type)
Type
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:54 Inverse-T #:Inactive SPS O
_:52 Inverse-T #:Behavior ENS O
_:53 Inverse-T #:Health ENS O
_:55 Inverse-T #:Pickup ACD O
_:300 Inverse-T #:Pickup loop AB SPS O
_:301 Inverse-T #:Pickup loop BC SPS O
_:302 Inverse-T #:Pickup loop CA SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:57 Inverse-T #:Operate ACT O
7.16.10
Protection and Automation Functions
7.16 Undervoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual 817
C53000-G5040-C015-9, Edition 11.2017