Additional Parameters for the Three-Winding Transformer and for the Grid Coupling Transformer
Parameter: Vmin threshold w1
Default setting (_:129) Vmin threshold w1 = 105.000 V
Parameter: Vmin threshold w2
Default setting (_:148) Vmin threshold w2 = 105.000 V
Parameter: Vmax threshold w1
Default setting (_:132) Vmax threshold w1 = 115.000 V
Parameter: Vmax threshold w2
Default setting (_:149) Vmax threshold w2 = 115.000 V
Blockings
Parameter: Blocking behavior
Default setting (_:14011:134) Blocking behavior = Auto-Manual
If the corresponding voltage limits are exceeded in either direction, the blockings prevent a change to a lower
or higher tap. On the one hand, this prevents excessive wear of the contacts of the tap changer and, on the
other hand, it prevents a system incident. With the parameter Blocking behavior, you set whether these
blockings are effective only in automatic operation or in both automatic and manual operation.
Parameter: V< Blocking
Default setting (_:14011:135) V< Blocking = on
Parameter: V< Threshold
Default setting (_:14011:136) V< Threshold = 90.000 V
Parameter: V< Time delay
Default setting (_:14011:137) V< Time delay = 0 s
Parameter: I> Blocking
Default setting (_:14011:138) I> Blocking = on
Parameter: I> Threshold
Default setting (_:14011:139) I> Threshold = 150 %
Parameter: I> Time delay
Default setting (_:14011:140) I> Time delay = 0 s
If the load current exceeds the threshold value I> Threshold for the time I> Time delay, the overcur-
rent blocking prevents changing to a higher or lower tap. Set the threshold value I> Threshold in % in rela-
tion to the rated current. To do this, set the parameter I reference for % values.
Parameter: I< Blocking
Default setting (_:14011:141) I< Blocking = off
Parameter: I< Threshold
Default setting (_:14011:142) I< Threshold = 10 %
Parameter: I< Time delay
Default setting (_:14011:143) I< Time delay = 10 s
If the load current drops below the threshold value I< Threshold for the time I< Time delay, the under-
current blocking prevents changing to a higher or lower tap. Set the threshold value I< Threshold in % in
relation to the rated current. To do this, set the parameter I reference for % values.
6.9.4.6
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 499
C53000-G5040-C015-9, Edition 11.2017