Addr. Parameter C Setting Options Default Setting
_:16351:148 90V V.contr.gc:Vmin
threshold w2
10.000 V to 340.000 V 105.000 V
_:16351:130 90V V.contr.gc:Vmin
time delay
0 s to 20 s 10 s
_:16351:131 90V V.contr.gc:Vmax
limiting
off
on
on
_:16351:132 90V V.contr.gc:Vmax
threshold w1
10.000 V to 340.000 V 115.000 V
_:16351:149 90V V.contr.gc:Vmax
threshold w2
10.000 V to 340.000 V 115.000 V
_:16351:133 90V V.contr.gc:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:16351:134 90V V.contr.gc:Blocking
behavior
Auto
Auto-Manual
Auto-Manual
_:16351:135 90V V.contr.gc:V<
Blocking
off
on
on
_:16351:136 90V V.contr.gc:V<
Threshold w1
10.000 V to 340.000 V 90.000 V
_:16351:150 90V V.contr.gc:V<
Threshold w2
10.000 V to 340.000 V 90.000 V
_:16351:137 90V V.contr.gc:V< Time
delay
0 s to 20 s 0 s
_:16351:138 90V V.contr.gc:I>
Blocking
off
on
on
_:16351:139 90V V.contr.gc:I>
Threshold
10 % to 500 % 150 %
_:16351:140 90V V.contr.gc:I> Time
delay
0 s to 20 s 0 s
_:16351:141 90V V.contr.gc:I<
Blocking
off
on
off
_:16351:142 90V V.contr.gc:I<
Threshold
3 % to 100 % 10 %
_:16351:143 90V V.contr.gc:I< Time
delay
0 s to 20 s 10 s
Information List
Two-Winding Transformer and Parallel Control
No.
Information Data Class
(Type)
Type
General
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
90V V.contr.2w
_:14011:81 90V V.contr.2w:>Block SPS I
_:14011:85 90V V.contr.2w:>Reset min./max. SPS I
_:14011:53 90V V.contr.2w:Health ENS O
_:14011:54 90V V.contr.2w:Inactive SPS O
6.9.6
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 509
C53000-G5040-C015-9, Edition 11.2017