Addr. Parameter C Setting Options Default Setting
_:16351:113 90V V.contr.gc:Band-
width
0.2 % to 10.0 % 1.0 %
_:16351:114 90V V.contr.gc:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:16351:115 90V V.contr.gc:T1 delay 5 s to 600 s 40 s
_:16351:116 90V V.contr.gc:T1
Inverse Min
5 s to 100 s 5 s
_:16351:117 90V V.contr.gc:T2 delay 0 s to 100 s 5 s
_:16351:118 90V V.contr.gc:Fast step
up
•
off
•
on
off
_:16351:119 90V V.contr.gc:Fast step
up limit
-50.0 % to 0.0 % -6.0 %
_:16351:120 90V V.contr.gc:Fast step
up T delay
0.0 s to 10.0 s 2.0 s
_:16351:121 90V V.contr.gc:Fast step
down
•
off
•
on
on
_:16351:122 90V V.contr.gc:Fast step
down limit
0.0 % to 50.0 % 6.0 %
_:16351:123 90V V.contr.gc:Fast step
down T delay
0.0 s to 10.0 s 0.0 s
_:16351:124 90V V.contr.gc:Function
monitoring
0 min to 120 min 15 min
_:16351:162 90V V.contr.gc:Power-
flow supervision
•
off
•
on
on
_:16351:163 90V V.contr.gc:Regulate
with T2 at start
•
off
•
on
on
_:16351:171 90V V.contr.gc:Set point
mode active
•
off
•
on
on
Line drop comp.
_:16351:125 90V V.contr.gc:Line drop
compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:16351:126 90V V.contr.gc:Target
voltage rising w1
0.0 % to 20.0 % 4.0 %
_:16351:147 90V V.contr.gc:Target
voltage rising w2
0.0 % to 20.0 % 4.0 %
_:16351:127 90V V.contr.gc:Max load
current
0.0 % to 500.0 % 100.0 %
_:16351:153 90V V.contr.gc:R line w1 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:154 90V V.contr.gc:X line w1 -30.0 Ω to 30.0 Ω 0.0 Ω
_:16351:155 90V V.contr.gc:R line w2 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:156 90V V.contr.gc:X line w2 -30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:16351:102 90V V.contr.gc:Lower
tap-position limit
-128 to 127 1
_:16351:103 90V V.contr.gc:Higher
tap-position limit
-128 to 127 15
_:16351:128 90V V.contr.gc:Vmin
limiting
•
off
•
on
on
_:16351:129 90V V.contr.gc:Vmin
threshold w1
10.000 V to 340.000 V 105.000 V
Control Functions
6.9 Voltage Controller
508 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017