Grid Coupling Transformer
Addr. Parameter C Setting Options Default Setting
Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
General
_:16351:1 90V V.contr.gc:Mode
•
off
•
on
•
test
on
_:16351:101 90V V.contr.gc:Oper-
ating mode
•
Manual
•
Auto
Manual
_:16351:157 90V V.contr.gc:Winding
selection
•
Winding 1
•
Winding 2
•
WithMaxLoad
Winding 1
_:16351:161 90V V.contr.gc:Winding
selection
•
Winding 1
•
Winding 2
Winding 1
Control tap changer
_:16351:107 90V V.contr.gc:Check
switching authority
•
no
•
yes
yes
_:16351:109 90V V.contr.gc:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:16351:110 90V V.contr.gc:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:16351:111 90V V.contr.gc:Feedback
monitoring time
0.01 s to 1800.00 s 10.00 s
Voltage Control
_:16351:164 90V V.contr.gc:Number
of target voltage
•
1
•
2
•
3
•
4
1
_:16351:112 90V V.contr.gc:Target
voltage 1 w1
10.000 V to 340.000 V 110.000 V
_:16351:165 90V V.contr.gc:Target
voltage 2 w1
10.000 V to 340.000 V 110.000 V
_:16351:166 90V V.contr.gc:Target
voltage 3 w1
10.000 V to 340.000 V 110.000 V
_:16351:167 90V V.contr.gc:Target
voltage 4 w1
10.000 V to 340.000 V 110.000 V
_:16351:146 90V V.contr.gc:Target
voltage 1 w2
10.000 V to 340.000 V 110.000 V
_:16351:168 90V V.contr.gc:Target
voltage 2 w2
10.000 V to 340.000 V 110.000 V
_:16351:169 90V V.contr.gc:Target
voltage 3 w2
10.000 V to 340.000 V 110.000 V
_:16351:170 90V V.contr.gc:Target
voltage 4 w2
10.000 V to 340.000 V 110.000 V
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 507
C53000-G5040-C015-9, Edition 11.2017