Selection Button Description
Manual settings (local time zone and daylight saving
time regulation)
This setting must be selected if you want to select the
local time zone and daylight saving time zone regula-
tions of your SIPROTEC 5 device regardless of the PC
settings.
Input: Offset time zone for GMT [min]
Selection: Switchover to daylight saving time
[yes/no] via check box
Input: Start of daylight saving time [Day and
time]
Input: End of daylight saving time [Day and
time]
Input: Offset daylight saving time [min]
Default settings as in the picture above
Settings
Addr. Parameter C Setting Options Default Setting
Time sync.
_:102 Time sync.:Time source
1
none
IRIG-B
DCF77
PI
SNTP
IEC 60870-5-103
PROFIBUS DP
Modbus
DNP3
IEEE 1588
IEC 60870-5-104
none
_:103 Time sync.:Time source
1 port
port J
port F
port E
port P
port N
port G
_:104 Time sync.:Time source
1 channel
Ch1
Ch2
_:105 Time sync.:Time source
2
none
IRIG-B
DCF77
PI
SNTP
IEC 60870-5-103
PROFIBUS DP
Modbus
DNP3
IEEE 1588
IEC 60870-5-104
none
3.6.5
System Functions
3.6 Date and Time Synchronization
SIPROTEC 5, High-Voltage Bay Controller, Manual 135