i
NOTE
With the P, Q sign parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see chapter 9.2 Structure of the Function, section on the
Inversion of Output-Related Measured and Statistical Values):
Active energy, output: Wp+
Active energy, input: Wp-
Reactive energy, output: Wq+
Reactive energy, input: Wq-
Application and Setting Notes for Energy Values
The set parameters apply for all electricity meters of the device. You find the setting parameters in DIGSI in the
project tree under Settings > Device settings.
Parameter: Energy restore interval
Default setting: (_:111) Energy restore interval = 10 min
Parameter Value Description
0 min
Restoring deactivated
60 min
Cyclical restoring after the set time 1 minute to 60 minutes
Note: If the parameter is activated through a time setting, the parameter Energy restore time is not in
effect and will be deactivated automatically.
Parameter: Energy restore time
Default setting: (_:112) Energy restore time = none
Parameter Value
Description
none
Deactivated
hh:00
Restoring on the full hour
hh:15
Restoring 15 minutes after the full hour
hh:30
Restoring 30 minutes after the full hour
hh:45
Restoring 45 minutes after the full hour
Note: If the parameter is activated through a time setting, the parameter Energy restore interval is
not in effect and will be deactivated automatically.
Parameter: Energy restore
Default setting: (_:120) Energy restore = latest value
Parameter Value
Description
latest value
Restoring of the current energy value
delta value
Restoring the difference value between the current energy value and the
energy value of the last restoring operation
Parameter: Energy restore by A.time
Default setting: (_:121) Energy restore by A.time = false
Parameter Value
Description
False
Restoring deactivated
9.9.2
Measured Values, Energy Values, and Supervision of the Primary System
9.9 Energy Values
SIPROTEC 5, High-Voltage Bay Controller, Manual 1043
C53000-G5040-C015-9, Edition 11.2017