Parameter Value Description
True
The cyclic restoring after the set time of the parameter (_:111) Energy
restore intervalwill also be synchronized with the system time.
Example: Energy restore interval = 30 min; current system time:
12:10 o'clock First restore: 12:30 o'clock; next restore: 13:00 o'clock etc.
Note: When the parameter is activated, the following setting values are possible for the parameter (_:111)
Energy restore interval: 1 min; 2 min; 3 min; 4 min; 5 min; 6 min; 10 min; 12 min; 15 min; 20 min;
30 min; 60 min.
Input Signals: >Restoring and >Resetting
Binary Inputs Description
>Restoring The restoring of the metered values is initiated via a binary input.
>Reset The metered value memory is set to 0 through the binary input.
You route these logical signals in the DIGSI routing matrix. Open the function group, for example, Line, where
you created the energy value. There, under the tab Measured values you will find the tab Energy, 3-phase.
In this tab, you will find the logical signals in addition to the measured values.
Measured Values, Energy Values, and Supervision of the Primary System
9.9 Energy Values
1044 SIPROTEC 5, High-Voltage Bay Controller, Manual