Application Templates and Functional Scope for Device 6MD86
Application templates are available in DIGSI 5 for the applications of device 6MD86.
The application templates contain:
Basic configurations
Required functions
Default settings
The following application templates are available for the device 6MD86 in the DIGSI 5 function library:
Not preconfigured
Double busbar
1.5 circuit breaker, type 1
1.5 circuit breaker, type 2
To load the application templates to the device, the following minimum hardware configuration requirements
must be met:
Application Templates Hardware Configuration
Template 1 Double busbar 8 binary inputs (BI), 15 binary
outputs (BO), 4 I, 4 V
Template 2 1.5 circuit breaker, type 1 42 BI, 38 BO, 8 I, 8 V
Template 3 1.5 circuit breaker, type 2 42 BI, 32 BO, 8 I, 8 V
The following table shows the functional scope and the function-point requirements of the application
templates described below:
Table 4-2
Functional Scope of the Application Templates for Device 6MD86
ANSI Function Abbr.
Points
Template 1
Template 2
Template 3
25 Synchrocheck, synchronizing function 0 x x x
27 Undervoltage protection, 3-phase V< 5
27 Undervoltage protection, 3-phase,
universal, Vx
Vx<
5
32/37 Power protection active/reactive power P<>, Q<> 10
38 Temperature supervision θ> 0
46 Negative-sequence protection, non-direc-
tional
I
2
>
10
49 Thermal overload protection
θ, I
2
t
0
50/51 TD Overcurrent protection, phases I> 0 x 2 x
50N/51N TD Overcurrent protection, ground IN> 10
67 Directional time-overcurrent protection,
phases
I>, ∠ (V,I) 35
67N Directional time-overcurrent protection,
ground
35
51V Overcurrent protection, voltage-dependent t = f(V,I) 10
50HS Instantaneous high-current tripping I>>> 0
50BF Circuit-breaker failure protection 15 x
59 Overvoltage protection, 3-phase V> 5
4.3