Settings
Addr. Parameter C Setting Options Default Setting
Trip logic
_:101 Trip logic:Trip at 2ph short
circuit
3-pole
1-pole, leading phase
1-pole, lagging phase
3-pole
_:102 Trip logic:3-pole coupling
with pickup
with trip
with trip
_:103 Trip logic:Reset of trip
command
with I<
with I< & aux.contact
with dropout
with I<
Information List
No. Information Data Class
(Type)
Type
Trip logic
_:300 Trip logic:Trip indication ACT O
Circuit Breaker
Overview
The Circuit-breaker function block represents the physical switch in the SIPROTEC 5 device.
The basic tasks of this function block are the operation of the circuit breaker and the acquisition of the circuit-
breaker auxiliary contacts and other circuit-breaker information.
The Circuit-breaker function block also provides information about:
Number of switching cycles
Breaking current, breaking voltage, and breaking frequency
Summation breaking current
Tripping, Opening, and Closing the Circuit Breaker
The circuit breaker is operated in the following situations:
Tripping of the circuit breaker as a result of a protection trip command
Opening of the circuit breaker as a result of control operations
Closing of the circuit breaker as a result of automatic reclosing or control operations
Tripping is always the result of a protection function. The operate indications of the individual protection func-
tions are summarized in the Trip logic function block. The trip command that causes the tripping in the
Circuit breaker function block is generated there. 1-pole or 3-pole tripping is possible depending on the
configuration, parameterization or even the protection function (see also 5.6.4.1 Function Description ).
To operate the circuit breaker, the Circuit-breaker function block provides the output signals (see Table 5-7)
that must be routed to the corresponding binary outputs of the device.
5.6.4.3
5.6.4.4
5.6.5
5.6.5.1
5.6.5.2
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
236 SIPROTEC 5, High-Voltage Bay Controller, Manual