EasyManua.ls Logo

Siemens 6MD86 - Operational Measured Values and Statistical Values

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operational Measured Values and Statistical Values
The following applies to the tolerances of currents and voltages:
The values apply both to the RMS values and the absolute value and phase angle of the fundamental
components.
The values were determined for pure sinusoidal signals – without harmonics.
Voltages
V
A
, V
B
, V
C
Voltage range
V secondary
< 200 V secondary
Secondary rated voltage
Measuring range
Frequency range
100 V to 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned
measuring range
V
AB
, V
BC
, V
CA
Voltage range
V secondary
< 200 V
Secondary rated voltage
Measuring range
Frequency range
100 V bis 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned
measuring range
Currents, Instrument Transformers
I
A
, I
B
, I
C
, 3I
0
Current range
A secondary
< 1:6 I
nenn
Rated currents
Measuring range
Frequency range
1 A, 5 A
(0.1 to 1.6) · I
rated
49 Hz to 51 Hz at f
rated
= 50 Hz
59 Hz to 61 Hz at f
rated
= 60 Hz
Tolerance 0.1 % of the measured value in the above mentioned
measuring range
Frequency range (expanded) 40 Hz to 60 Hz at f
rated
= 50 Hz
50 Hz to 70 Hz at f
rated
= 60 Hz
Tolerance 0.3 % of the measured value in the above mentioned
measuring range
11.46
Technical Data
11.46 Operational Measured Values and Statistical Values
SIPROTEC 5, High-Voltage Bay Controller, Manual 1195
C53000-G5040-C015-9, Edition 11.2017

Table of Contents