No. Information Data Class
(Type)
Type
Sensor 9
_:11619:52 Sensor 9:Health ENS O
_:11619:60 Sensor 9:Failure SPS O
_:11619:80 Sensor 9:TmpOut MV O
Sensor 10
_:11611:52 Sensor 10:Health ENS O
_:11611:60 Sensor 10:Failure SPS O
_:11611:80 Sensor 10:TmpOut MV O
Sensor 11
_:11611:52 Sensor 11:Health ENS O
_:11611:60 Sensor 11:Failure SPS O
_:11611:80 Sensor 11:TmpOut MV O
Sensor 12
_:11611:52 Sensor 12:Health ENS O
_:11611:60 Sensor 12:Failure SPS O
_:11611:80 Sensor 12:TmpOut MV O
Communication with RTD Unit
Integration of a Serial RTD Unit (Ziehl TR1200)
Connection of the Communication Lines
Figure 5-81 shows how you connect the RTD box to the SIPROTEC 5 device. Note that Pin 1 of the RJ45 plug is
connected to RTD-B and Pin 2 is connected to RTD-A.
[dwverbau-201112-01.tif, 1, en_US]
Figure 5-81 Connection of the RTD Unit to the SIPROTEC 5 Device
Adding a USART Module
Add a USART-AB-1EL or a USART-AC-2EL USART module in DIGSI to the device. The USART module must be
inserted at one of the plug-in positions for communication modules in the base module or in the CB202
expansion module (refer to the following figure).
5.7.9
5.7.9.1
Function-Group Types
5.7 Function-Group Type Analog Units
286 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017