Addr. Parameter C Setting Options Default Setting
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 User curve #:Time dial 0.05 to 15.00 1.00
Information List
No. Information Data Class
(Type)
Type
User curve #
_:81 User curve #:>Block stage SPS I
_:501 User curve #:>Release delay & op. SPS I
_:84 User curve #:>Activ. dyn. settings SPS I
_:500 User curve #:>Block delay & op. SPS I
_:54 User curve #:Inactive SPS O
_:52 User curve #:Behavior ENS O
_:53 User curve #:Health ENS O
_:60 User curve #:Inrush blocks operate SPS O
_:62 User curve #:Dyn.set. AR cycle1act. SPS O
_:63 User curve #:Dyn.set. AR cycle2act. SPS O
_:64 User curve #:Dyn.set. AR cycle3act. SPS O
_:65 User curve #:Dyn.set. ARcycl.>3act SPS O
_:66 User curve #:Dyn.set. CLP active SPS O
_:67 User curve #:Dyn.set. BI active SPS O
_:68 User curve #:Dyn. set. blks. pickup SPS O
_:59 User curve #:Disk emulation running SPS O
_:55 User curve #:Pickup ACD O
_:300 User curve #:Direction ACD O
_:56 User curve #:Operate delay expired ACT O
_:57 User curve #:Operate ACT O
Influence of Other Functions via Dynamic Settings
7.5.8.1 Description and 7.5.8.2 Application and Setting Notes (Advanced Stage) describe the influence of
other functions on dynamic settings.
7.7.9.4
7.7.10
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 745
C53000-G5040-C015-9, Edition 11.2017