Application Templates and Functional Scope for Device 6MD85
Application templates are available in DIGSI 5 for the applications of the device 6MD85.
The application templates contain:
•
Basic configurations
•
Required functions
•
Default settings
The following application templates are available for the device 6MD85 in the DIGSI 5 function library:
•
Not preconfigured
•
Standard
•
Control expanded
To load the application templates to the device, the following minimum hardware configuration requirements
must be met:
Application Templates Hardware Configuration
Template 1 Standard 8 binary inputs (BI), 15 binary
outputs (BO), 4 I, 4 V
Template 2 Control expanded 8 BI, 15 BO, 4 I, 4 V
The following table shows the functional scope and the function-point requirements of the application
templates:
Table 4-1
Functional Scope of the Application Templates for Device 6MD85
ANSI Function Abbr.
Points
Template 1
Template 2
25 Synchrocheck, synchronizing function 50
27 Undervoltage protection, 3-phase V< 5
27 Undervoltage protection, 3-phase, universal,
Vx
Vx< 5
32/37 Power protection active/reactive power P<>, Q<> 10
38 Temperature supervision θ> 0
46 Negative-sequence protection, non-directional I
2
> 10
49 Thermal overload protection
θ, I
2
t
0
50/51 TD Overcurrent protection, phases I> 20
50N/51N TD Overcurrent protection, ground IN> 20
67 Directional time-overcurrent protection,
phases
I>, ∠ (V,I) 35
67N Directional time-overcurrent protection,
ground
35
51V Overcurrent protection, voltage dependent t = f(V,I) 10
50HS Instantaneous high-current tripping I>>> 0
59 Overvoltage protection, 3-phase V> 5
59 Overvoltage protection, positive-sequence
system
V1> 5
59 Overvoltage protection, 3-phase, universal, Vx Vx> 5
74TC Trip-circuit supervision 0
81O Overfrequency protection f> 5
4.2
Applications
4.2 Application Templates and Functional Scope for Device 6MD85
SIPROTEC 5, High-Voltage Bay Controller, Manual 175
C53000-G5040-C015-9, Edition 11.2017