ANSI Function Abbr.
Points
Template 1
Template 2
81U Underfrequency protection f< 5
Underfrequency Load Shedding 15
81R Frequency change protection df/dt 5
86 Lockout 0
90V Two-winding transformer voltage controller 150
90V Three-winding transformer voltage controller 200
90V Grid coupling transformer voltage controller 175
PMU Phasor measurement unit PMU 40
Circuit-breaker supervision
∑Ix, I
2
t, 2P, Make
time
10
SOTF Instantaneous tripping at switch onto fault SOTF 0
Arc protection 0
Signaling-voltage supervision 0
External synchronization 0
External 1-of-n check 0
Measured values, standard 0 x x
Measured values, extended: min/max/average
values
3
b)
4
Switching statistic counters 0 x x
CFC standard 0 x x
CFC arithmetic 40
Switching sequence 5 x
Inrush-current detection 0
External trip initiation 0
Control 0
Fault recording of analog and binary signals 0
Supervision 0 x x
Protection interface, serial 0
Circuit breaker
3
a)
Circuit-breaker control
3
a)
1 1
Circuit-breaker status
3
a)
Disconnector/grounding conductor
3
a)
3 3
Disconnector/grounding conductor status
3
a)
Function points: 0 52
a) Points apply beginning with the 5th element
b) 3 Function points per type used
Application Template: 6MD85 Unconfigured
The unconfigured application template is available for all applications that cannot be built on other application
templates or for which deletion would be too complex.
Application Template: 6MD85 Standard
The 6MD85 standard application template is preconfigured for the following applications:
•
Double busbar feeder with switchgear interlocking protection
Applications
4.2 Application Templates and Functional Scope for Device 6MD85
176 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017