Addr. Parameter C Setting Options Default Setting
_:114
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Delay T2
for 1-pole trip
0.050 s to 60.000 s 0.130 s
_:115
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Minimum
operate time
0.00 s to 60.00 s 0.10 s
_:120 50BF Ad.CBF #:3I0 crite-
rion
•
Direct release
•
Plausibility check
Plausibility
check
_:121 50BF Ad.CBF #:I2 crite-
rion
•
Direct release
•
Plausibility check
Plausibility
check
_:122 50BF Ad.CBF #:Threshold
3I0 dir. release
1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:123 50BF Ad.CBF #:Threshold
I2 dir. release
1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:124 50BF Ad.CBF #:Monit.
time for BI ">Start"
0.05 s to 60.00 s 15.00 s
_:125 50BF Ad.CBF
#:Monit.tm. f.BI
">Release"
0.05 s to 60.00 s 15.00 s
Information List
No.
Information Data Class
(Type)
Type
50BF Ad.CBF #
_:501
(1/3-pole circuit
breaker)
50BF Ad.CBF #:>Start 3-pole SPS I
_:501
(3-pole circuit
breaker)
50BF Ad.CBF #:>Start SPS I
_:502
(1/3-pole circuit
breaker)
50BF Ad.CBF #:>Start pole A SPS I
_:502
(3-pole circuit
breaker)
50BF Ad.CBF #:>Release SPS I
_:503
(1/3-pole circuit
breaker)
50BF Ad.CBF #:>Start pole B SPS I
_:503
(3-pole circuit
breaker)
50BF Ad.CBF #:>CB defect SPS I
7.1.6
Protection and Automation Functions
7.1 Circuit-Breaker Failure Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual 539
C53000-G5040-C015-9, Edition 11.2017