EasyManua.ls Logo

Siemens 6MD86 - Cooperation with External Automatic Reclosing Function; Description

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Information Data Class
(Type)
Type
_:6601:330 General:Blk.by action time exp SPS O
_:6601:331 General:Blk.by max.d.t. expiry SPS O
_:6601:337 General:Block. by no cycle SPS O
_:6601:338 General:Block. by protection SPS O
_:6601:335 General:Blk.by loss of voltage SPS O
_:6601:336 General:Block. by max. cycles SPS O
_:6601:339 General:Cyc1 1p AR INS O
_:6601:340 General:Cyc1 3p AR INS O
ADT
_:6631:51 ADT:Mode (controllable) ENC C
_:6631:501 ADT:>Remote close signal SPS I
_:6631:52 ADT:Behavior ENS O
_:6631:53 ADT:Health ENS O
_:6631:301 ADT:ADT is running SPS O
_:6631:302 ADT:Stage release prot. SPS O
_:6631:303 ADT:Synchrocheck request SPS O
Cooperation with External Automatic Reclosing Function
Description
The operation of an external reclosing device with the SIPROTEC protection device occurs through the function
mode Operation with external automatic reclosing function. In this function mode, the SIPROTEC protec-
tion functions create the trip command and the external reclosing device creates the close command.
The following figure shows the interaction of an external reclosing device with the functions of the SIPROTEC
5 device.
7.2.6
7.2.6.1
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 583
C53000-G5040-C015-9, Edition 11.2017

Table of Contents