Addr. Parameter C Setting Options Default Setting
_:18 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:111 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: bin.input
_:34 Log.-inv.-T #:Effected by
binary input
•
no
•
yes
no
_:41 Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
_:19 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:112 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Information List
No.
Information Data Class
(Type)
Type
Log.-inv.-T #
_:81 Log.-inv.-T #:>Block stage I
_:501 Log.-inv.-T #:>Release delay & op. I
_:84 Log.-inv.-T #:>Activ. dyn. settings I
_:500 Log.-inv.-T #:>Block delay & op. I
_:54 Log.-inv.-T #:Inactive O
_:52 Log.-inv.-T #:Behavior O
_:53 Log.-inv.-T #:Health O
_:60 Log.-inv.-T #:Inrush blocks operate O
_:62 Log.-inv.-T #:Dyn.set. AR cycle1act. O
_:63 Log.-inv.-T #:Dyn.set. AR cycle2act. O
_:64 Log.-inv.-T #:Dyn.set. AR cycle3act. O
_:65 Log.-inv.-T #:Dyn.set. ARcycl.>3act O
_:66 Log.-inv.-T #:Dyn.set. CLP active O
_:67 Log.-inv.-T #:Dyn.set. BI active O
_:68 Log.-inv.-T #:Dyn. set. blks. pickup O
_:55 Log.-inv.-T #:Pickup O
_:300 Log.-inv.-T #:Direction O
_:56 Log.-inv.-T #:Operate delay expired O
_:57 Log.-inv.-T #:Operate O
7.7.7.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 735
C53000-G5040-C015-9, Edition 11.2017