Addr. Parameter C Setting Options Default Setting
_:14 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 2
_:30 Log.-inv.-T #:Effected by
AR cycle 2
no
yes
no
_:37 Log.-inv.-T #:Stage
blocked
no
yes
no
_:15 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:108 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 3
_:31 Log.-inv.-T #:Effected by
AR cycle 3
no
yes
no
_:38 Log.-inv.-T #:Stage
blocked
no
yes
no
_:16 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.s: AR cycle>3
_:32 Log.-inv.-T #:Effected by
AR cycle gr. 3
no
yes
no
_:39 Log.-inv.-T #:Stage
blocked
no
yes
no
_:17 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 Log.-inv.-T #:Time dial 0.000 s to 60.000 s 1.250 s
Dyn.s: Cold load PU
_:33 Log.-inv.-T #:Effect. b.
cold-load pickup
no
yes
no
_:40 Log.-inv.-T #:Stage
blocked
no
yes
no
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
734 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017