Addr. Parameter C Setting Options Default Setting
_:110 External sync.:Direct
close command
•
0
•
1
false
Information List
No. Information Data Class
(Type)
Type
External sync.
_:506 External sync.:>Synch. device ready SPS I
_:508 External sync.:>In progress SPS I
_:507 External sync.:>Close cmd. released SPS I
_:509 External sync.:>Op. mode 'dir.cls.cmd' SPS I
_:52 External sync.:Behavior ENS O
_:54 External sync.:Health ENS O
_:55 External sync.:Start syn. process SPS O
_:56 External sync.:Stop syn. process SPS O
_:57 External sync.:Start/stop syn. proc. SPS O
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2311:127 General:Angle adjust.
(transform.)
-179.0 ° to 180.0 ° 0.0 °
General
_:5071:1 Synchrocheck 1:Mode
•
off
•
on
•
test
off
_:5071:101 Synchrocheck 1:Min. oper-
ating limit Vmin
0.300 V to 340.000 V 90.000 V
_:5071:102 Synchrocheck 1:Max.
operat. limit Vmax
0.300 V to 340.000 V 110.000 V
_:5071:110 Synchrocheck 1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞ 30.00 s
_:5071:108 Synchrocheck 1:Direct close
command
•
no
•
yes
no
_:5071:126 Synchrocheck 1:Voltage
adjustment
0.500 to 2.000 1.000
De-en.gized switch.
_:5071:105 Synchrocheck 1:Close cmd.
at V1< & V2>
•
no
•
yes
no
_:5071:106 Synchrocheck 1:Close cmd.
at V1> & V2<
•
no
•
yes
no
_:5071:107 Synchrocheck 1:Close cmd.
at V1< & V2<
•
no
•
yes
no
_:5071:103 Synchrocheck 1:V1, V2
without voltage
0.300 V to 170.000 V 5.000 V
_:5071:104 Synchrocheck 1:V1, V2
with voltage
0.300 V to 340.000 V 80.000 V
6.4.14.4
6.4.15
Control Functions
6.4 Synchronization Function
420 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017