Addr. Parameter C Setting Options Default Setting
_:124 Syn./Asy.bal.#:Max.
angle diff. α2>α1
0 ° to 90 ° 10 °
_:125 Syn./Asy.bal.#:Max.
angle diff. α2<α1
0 ° to 90 ° 10 °
_:121 Syn./Asy.bal.#:Delay
close command
0.00 s to 60.00 s 0.00 s
Balancing V
_:131 Syn./Asy.bal.#:Balancing
voltage V2
off
transformer tap
balancing pulses
off
_:132 Syn./Asy.bal.#:T V pulse
min
0.01 s to 1.00 s 0.10 s
_:133 Syn./Asy.bal.#:T V pulse
max
0.01 s to 60.00 s 1.00 s
_:134 Syn./Asy.bal.#:dV per
second
0 V/s to 0 V/s 0 V/s
_:135 Syn./Asy.bal.#:T pause V 0.10 s to 60.00 s 5.00 s
_:136 Syn./
Asy.bal.#:Smoothing
1 to 100 1
_:137 Syn./Asy.bal.#:(V/
Vrated)/(f/frated)
1.00 to 1.40 1.10
Balancing f
_:141 Syn./Asy.bal.#:Balancing
frequency f2
off
balancing pulses
off
_:142 Syn./Asy.bal.#:T f pulse
min
0.01 s to 1.00 s 0.10 s
_:143 Syn./Asy.bal.#:T f pulse
max
0.01 s to 60.00 s 1.00 s
_:144 Syn./Asy.bal.#:df/dt of
the controller
0.05 Hz/s to 5.00 Hz/s 1.00 Hz/s
_:145 Syn./Asy.bal.#:T pause f 0.10 s to 60.00 s 5.00 s
_:146 Syn./Asy.bal.#:Δf set
point for balancing
-1.00 Hz to 1.00 Hz 0.04 Hz
_:147 Syn./
Asy.bal.#:Smoothing
1 to 100 1
_:148 Syn./Asy.bal.#:T close
without balancing
1.00 s to 100.00 s 5.00 s
_:149 Syn./Asy.bal.#:Release
for the kick pulse
off
on
off
_:150 Syn./Asy.bal.#:Δf for the
kick pulse
-1.00 Hz to 1.00 Hz 0.04 Hz
_:151 Syn./Asy.bal.#:Stabiliza-
tion
0 to 1000 0
Addr. Parameter C Setting Options Default Setting
External sync.
_:1 External sync.:Mode
off
on
test
on
_:109 External
sync.:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞ 30.00 s
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 419
C53000-G5040-C015-9, Edition 11.2017