Addr. Parameter C Setting Options Default Setting
_:12691:8 Inverse-T 1:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:12691:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:12691:108 Inverse-T 1:Type of char-
acter. curve
_:12691:109 Inverse-T 1:Reset
instantaneous
disk emulation
disk emulation
_:12691:101 Inverse-T 1:Time dial 0.05 to 15.00 1.00
Information List
No. Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Inverse-T 1
_:12691:81 Inverse-T 1:>Block stage SPS I
_:12691:500 Inverse-T 1:>Block delay & op. SPS I
_:12691:54 Inverse-T 1:Inactive SPS O
_:12691:52 Inverse-T 1:Behavior ENS O
_:12691:53 Inverse-T 1:Health ENS O
_:12691:60 Inverse-T 1:Inrush blocks operate ACT O
_:12691:59 Inverse-T 1:Disk emulation running SPS O
_:12691:55 Inverse-T 1:Pickup ACD O
_:12691:56 Inverse-T 1:Operate delay expired ACT O
_:12691:57 Inverse-T 1:Operate ACT O
Stage with User-Defined Characteristic Curve
Description
The User-defined characteristic curve overcurrent protection stage is only available in the advanced func-
tion type.
This stage is structured the same way as the stage with the inverse-time characteristic curve. The only differ-
ence is that you can define the characteristic curve as desired.
User-Defined Characteristic Curve
With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.
Pickup and Dropout Behaviors with the User-Defined Characteristic Curve
When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
7.8.4.4
7.8.5
7.8.5.1
Protection and Automation Functions
7.8 Overcurrent Protection, 1-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual 755
C53000-G5040-C015-9, Edition 11.2017