Default setting (_:14011:148) VT supervision time delay = 10 s
With the VT supervision time delay parameter, you set the time for which exceeding the voltage
supervision threshold does not lead to a blocking.
Parameter: Circul. current blocking
Default setting (_:14011:149) Circul. current blocking = on
With the Circul. current blocking parameter, you switch the supervision of the circulating reactive
current off or on.
Parameter: Circul. current threshold
Default setting (_:14011:150) Circul. current threshold = 150 %
With the Circul. current threshold parameter, you set the level at which the supervision must be acti-
vated.
Parameter: Circul. current time delay
Default setting (_:14011:151) Circul. current time delay = 30 s
With the Circul. current time delay parameter, you set the time for which exceeding the threshold
value of the circulating reactive current supervision does not lead to a blocking.
Settings
Two-Winding Transformer and Parallel Control
Addr. Parameter C Setting Options Default Setting
Ref. for %-values
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
_:2311:106 General:Rated app.
power transf.
0.20 MVA to 5000.00 MVA 692.82 MVA
_:2311:108 General:Imp(Z): short
circuit imp.
1.00 % to 20.00 % 10.00 %
General
_:14011:1 90V V.contr.2w:Mode
off
on
test
on
_:14011:101 90V V.contr.2w:Oper-
ating mode
Manual
Auto
Manual
Control tap changer
_:14011:107 90V V.contr.2w:Check
switching authority
no
yes
yes
_:14011:109 90V V.contr.2w:Control
model
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
SBO w. enh.
security
_:14011:110 90V V.contr.2w:SBO
time-out
0.01 s to 1800.00 s 30.00 s
_:14011:111 90V V.contr.2w:Feed-
back monitoring time
0.01 s to 1800.00 s 10.00 s
Voltage Control
_:14011:156 90V V.contr.2w:Number
of target voltage
1
2
3
4
1
6.9.5
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual 501
C53000-G5040-C015-9, Edition 11.2017