Addr. Parameter C Setting Options Default Setting
_:14011:112 90V V.contr.2w:Target
voltage 1
10.000 V to 340.000 V 110.000 V
_:14011:157 90V V.contr.2w:Target
voltage 2
10.000 V to 340.000 V 110.000 V
_:14011:158 90V V.contr.2w:Target
voltage 3
10.000 V to 340.000 V 110.000 V
_:14011:159 90V V.contr.2w:Target
voltage 4
10.000 V to 340.000 V 110.000 V
_:14011:113 90V V.contr.2w:Band-
width
0.2 % to 10.0 % 1.0 %
_:14011:114 90V V.contr.2w:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:14011:115 90V V.contr.2w:T1 delay 5 s to 600 s 40 s
_:14011:116 90V V.contr.2w:T1
Inverse Min
5 s to 100 s 5 s
_:14011:117 90V V.contr.2w:T2 delay 0 s to 100 s 5 s
_:14011:118 90V V.contr.2w:Fast step
up
•
off
•
on
off
_:14011:119 90V V.contr.2w:Fast step
up limit
-50.0 % to 0.0 % -6.0 %
_:14011:120 90V V.contr.2w:Fast step
up T delay
0.0 s to 10.0 s 2.0 s
_:14011:121 90V V.contr.2w:Fast step
down
•
off
•
on
on
_:14011:122 90V V.contr.2w:Fast step
down limit
0.0 % to 50.0 % 6.0 %
_:14011:123 90V V.contr.2w:Fast step
down T delay
0.0 s to 10.0 s 0.0 s
_:14011:124 90V V.contr.2w:Function
monitoring
0 min to 120 min 15 min
_:14011:155 90V V.contr.2w:Regulate
with T2 at start
•
off
•
on
on
_:14011:160 90V V.contr.2w:Set
point mode active
•
off
•
on
on
Parallel operation
_:14011:161 90V V.contr.2w:Parallel
mode
•
No mode
•
Master
•
Follower
•
Circulat. react current
No mode
_:14011:168 90V V.contr.2w:Parallel-
transfomer id
1 to 8 1
_:14011:164 90V V.contr.2w:Parallel
mode changeable
•
by setting
•
controllable
by setting
_:14011:165 90V V.contr.2w:Force
master changeable
•
by setting
•
controllable
by setting
_:14011:166 90V V.contr.2w:Maximal
tap difference
1 to 9 2
_:14011:169 90V V.contr.2w:Reactive
I control factor
0.01 to 100.00 1.00
_:14011:146 90V V.contr.2w:VT
supervision
•
off
•
on
on