tive automatic reclosing cycle will be completely blocked. With the binary input
>Block 79 cycle
, you can
block the associated automatic reclosing cycle.
For applications with 1-pole tripping, the cycle control provides a signal, based on which the protection func-
tions can recognize that the automatic reclosing function only occurs after 1-pole tripping (
AR only after
1p. trip
). The approval or switch over of special protection stages only occurs for types of faults that lead to
1-pole tripping.
[loauowrk-210311-01.tif, 1, en_US]
Figure 7-37
Cycle Control with Operating Mode: With Tripping/Without Action Time
Cycle Control with Operating Mode 4: With Pickup/Without Action Time
The cycle control checks the availability for each automatic reclosing cycle. In Figure 7-38, the cycle control for
the 1st automatic reclosing cycle and other reclosing cycles is illustrated. The further automatic reclosing
cycles are generally described with the cycle number n and apply for all other configured automatic reclosing
cycles.
7.2.4.9
Protection and Automation Functions
7.2 Automatic Reclosing Function
558 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017