Reading Indications from the PC with DIGSI 5
Procedure
Menu Path (Project) Log
Project → Device → Process data → Log → Operational log
Setting changes
Fault log
User indications 1
User indications 2
Motor-starting log
Ground-fault log
Online access → Device → Device information → Log
tab →
Device-diagnosis log
Security indications
Online access → Device → Test suite → Communica-
tion module →
Communication indications
To read the indications with DIGSI 5 your PC must be connected via the USB user interface of the on-site
operation panel or via an Ethernet interface of the device. You can establish a direct connection to your PC
via the Ethernet interfaces. It is also possible to access all connected SIPROTEC 5 devices via a data network
from your DIGSI 5 PC.
²
You access the desired logs of the SIPROTEC 5 device, use the project-tree window. If you have not
created the device within a project, you can also do this via the Online access menu item.
After selecting the desired log, you are shown the last state of the log loaded from the device. To update, it is
necessary to synchronize with the log in the device.
²
Synchronize the log. For this purpose, click the appropriate button in the headline of the log (see the
ground-fault indications example in Figure 3-2 a)).
[scgrflmd-191012-01, 1, en_US]
Figure 3-2 DIGSI 5 Display of an Indication List (Example of Ground-Fault Log)
You will find additional information about deleting and saving logs in chapter 3.1.6 Saving and Deleting the
Logs.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. You will find information about this in chapter 3.1.5.1 General.
3.1.3
System Functions
3.1 Indications
50 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017