Figure 3-1
On-Site Display of an Indication List (Example: Operational Indications)
Menu Path Log
Main menu → Indications → Operational log
Fault log
Ground-fault log
Setting changes
User indications 1
User indications 2
Motor-starting indications
Main Menu → Test & Diagnosis → Log → Device diagnosis
Security indications
Communication indications
To reach the desired log from the main menu, use the navigation keys of the on-site operation panel.
²
Navigate inside the log using the navigation keys (top/bottom). You will find the most current indication
at the top of the list. The selected indication is shown with a dark background.
Which indications can be shown in the selected log depends on the assignments in the DIGSI 5 information
routing matrix or is predefined. Every indication contains date, time and its state as additional information.
You will find information about this in chapter 3.1.5.1 General.
In some logs you are given the option of deleting the entire indication list by softkey in the footer of the
display. To learn more about this, read chapter 3.1.6 Saving and Deleting the Logs.
NOTE
No password entry is necessary to read indications from the device.
System Functions
3.1 Indications
SIPROTEC 5, High-Voltage Bay Controller, Manual 49
C53000-G5040-C015-9, Edition 11.2017