Addr. Parameter C Setting Options Default Setting
_:3 Log.inv.T KP #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.inv.T KP #:Time dial 0.05 to 1.50 0.20
_:101 Log.inv.T KP #:Knee-
point current
1 A @ 100 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.500 A
_:105 Log.inv.T KP #:Knee-
point time
0.00 s to 100.00 s 23.60 s
_:102 Log.inv.T KP #:Current at
Min. time
1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 Log.inv.T KP #:Min. time
of the curve
0.00 s to 30.00 s 0.80 s
_:103 Log.inv.T KP #:Max. time
of the curve
0.00 s to 200.00 s 93.00 s
Information List
No.
Information Data Class
(Type)
Type
Stage #
_:81 Log.inv.T KP #:>Block stage SPS I
_:501 Log.inv.T KP #:>Release delay & op. SPS I
_:500 Log.inv.T KP #:>Block delay & op. SPS I
_:54 Log.inv.T KP #:Inactive SPS O
_:52 Log.inv.T KP #:Behavior ENS O
_:53 Log.inv.T KP #:Health ENS O
_:60 Log.inv.T KP #:Inrush blocks operate SPS O
_:55 Log.inv.T KP #:Pickup ACD O
_:300 Log.inv.T KP #:Direction ACD O
_:56 Log.inv.T KP #:Operate delay expired ACT O
_:57 Log.inv.T KP #:Operate ACT O
7.7.8.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 739
C53000-G5040-C015-9, Edition 11.2017