No. Information Data Class
(Type)
Type
_:300 Manual close:Detected SPS O
Settings
Addr. Parameter C Setting Options Default Setting
Ref. for %-values
_:2311:101 General:Rated normal
current
0.20 A to 100000.00 A 1000.00 A
_:2311:102 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Breaker settings
_:2311:112 General:Current thresh.
CB open
1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:113 General:1-pole operate
allowed
•
no
•
yes
yes
_:2311:136 General:Op. mode BFP
•
unbalancing
•
I> query
unbalancing
Trip logic
_:5341:101 Trip logic:Trip at 2ph
short circuit
•
3-pole
•
1-pole, leading phase
•
1-pole, lagging phase
3-pole
_:5341:102 Trip logic:3-pole
coupling
•
with pickup
•
with trip
with trip
_:5341:103 Trip logic:Reset of trip
command
•
with I<
•
with I< & aux.contact
•
with dropout
with I<
Circuit break.
_:4261:101 Circuit break.:Output
time
0.02 s to 1800.00 s 0.10 s
_:4261:105 Circuit break.:Indicat. of
breaking values
•
with trip
•
always
always
Manual close
_:6541:101 Manual close:Action
time
0.01 s to 60.00 s 0.30 s
_:6541:102 Manual close:CB open
dropout delay
0.00 s to 60.00 s 0.00 s
Control
_:4201:101 Control:Control model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:4201:102 Control:SBO time-out 0.01 s to 1800.00 s 30.00 s
_:4201:103 Control:Feedback moni-
toring time
0.01 s to 1800.00 s 1.00 s
5.6.8
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual 249
C53000-G5040-C015-9, Edition 11.2017