Addr. Parameter C Setting Options Default Setting
_:4201:155 Control:Ident.
sw.auth. 1
Freely editable text
_:4201:156 Control:Ident.
sw.auth. 2
Freely editable text
_:4201:157 Control:Ident.
sw.auth. 3
Freely editable text
_:4201:158 Control:Ident.
sw.auth. 4
Freely editable text
_:4201:159 Control:Ident.
sw.auth. 5
Freely editable text
_:4201:154 Control:Multiple
specific sw.auth.
•
0
•
1
false
CB test
_:6151:101 CB test:Dead time 0.00 s to 60.00 s 0.10 s
_:6151:102 CB test:Trip only
•
0
•
1
false
_:6151:103 CB test:Consider
current criterion
•
0
•
1
false
_:6151:104 CB test:Current
threshold
1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
Information List
No.
Information Data Class
(Type)
Type
Trip logic
_:5341:300 Trip logic:Trip indication ACT O
Circuit break.
_:4261:500 Circuit break.:>Ready SPS I
_:4261:501 Circuit break.:>Acquisition blocking SPS I
_:4261:502 Circuit break.:>Reset switch statist. SPS I
_:4261:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:4261:503 Circuit break.:External health ENS I
_:4261:53 Circuit break.:Health ENS O
_:4261:58 Circuit break.:Position 3-pole DPC C
_:4261:459 Circuit break.:Position 1-pole phsA DPC C
_:4261:460 Circuit break.:Position 1-pole phsB DPC C
_:4261:461 Circuit break.:Position 1-pole phsC DPC C
_:4261:300 Circuit break.:Trip/open cmd. 3-pole SPS O
_:4261:401 Circuit break.:Trip only pole A SPS O
_:4261:402 Circuit break.:Trip only pole B SPS O
_:4261:403 Circuit break.:Trip only pole C SPS O
_:4261:301 Circuit break.:Close command SPS O
_:4261:302 Circuit break.:Command active SPS O
_:4261:303 Circuit break.:Definitive trip SPS O
6.2.2.5
Control Functions
6.2 Switching Devices
SIPROTEC 5, High-Voltage Bay Controller, Manual 323
C53000-G5040-C015-9, Edition 11.2017