EasyManua.ls Logo

Siemens 6MD86 - Page 324

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Information Data Class
(Type)
Type
_:4261:304 Circuit break.:Alarm suppression SPS O
_:4261:306 Circuit break.:Op.ct. INS O
_:4261:407 Circuit break.:Op.ct. A INS O
_:4261:408 Circuit break.:Op.ct. B INS O
_:4261:409 Circuit break.:Op.ct. C INS O
_:4261:307 Circuit break.:ΣI Brk. BCR O
_:4261:308 Circuit break.:ΣIA Brk. BCR O
_:4261:309 Circuit break.:ΣIB Brk. BCR O
_:4261:310 Circuit break.:ΣIC Brk. BCR O
_:4261:311 Circuit break.:Break.-current phs A MV O
_:4261:312 Circuit break.:Break.-current phs B MV O
_:4261:313 Circuit break.:Break.-current phs C MV O
_:4261:317 Circuit break.:Break. current 3I0/IN MV O
_:4261:314 Circuit break.:Break. voltage phs A MV O
_:4261:315 Circuit break.:Break. voltage phs B MV O
_:4261:316 Circuit break.:Break. voltage phs C MV O
_:4261:322 Circuit break.:CB open hours INS O
_:4261:323 Circuit break.:Operating hours INS O
Manual close
_:6541:501 Manual close:>Block manual close SPS I
_:6541:500 Manual close:>Input SPS I
_:6541:300 Manual close:Detected SPS O
Reset LED Group
_:13381:500 Reset LED Group:>LED reset SPS I
_:13381:320 Reset LED Group:LED have been reset SPS O
Control
_:4201:503 Control:>Sw. authority local SPS I
_:4201:504 Control:>Sw. authority remote SPS I
_:4201:505 Control:>Sw. mode interlocked SPS I
_:4201:506 Control:>Sw. mode non-interl. SPS I
_:4201:53 Control:Health ENS O
_:4201:58 Control:Cmd. with feedback DPC C
_:4201:302 Control:Switching auth. station SPC C
_:4201:308 Control:Enable sw. auth. 1 SPC C
_:4201:309 Control:Enable sw. auth. 2 SPC C
_:4201:310 Control:Enable sw. auth. 3 SPC C
_:4201:311 Control:Enable sw. auth. 4 SPC C
_:4201:312 Control:Enable sw. auth. 5 SPC C
_:4201:313 Control:Switching authority ENS O
_:4201:314 Control:Switching mode ENS O
Interlocking
_:4231:500 Interlocking:>Enable opening SPS I
_:4231:501 Interlocking:>Enable closing SPS I
_:4231:502 Interlocking:>Enable opening(fixed) SPS I
_:4231:503 Interlocking:>Enable closing (fixed) SPS I
_:4231:53 Interlocking:Health ENS O
Control Functions
6.2 Switching Devices
324 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017