Table 3-3 Metered Values
IEC 61850 Device Display/
DIGSI
Description
Validity
Good Invalid Questionable
X Value The metered value is invalid.
X --- The metered value was not calcu-
lated.
X ≈ Value The metered value has no refer-
ence.
Indication Columns
The following table shows the meaning of the individual columns in the log:
Indication Column Meaning
Time stamp Time stamp of the indication in device time using the local time
zone of the device or the query time for the motor log
Relative time Relative time to a reference entry
Error number Number of the error that occurred in the device. This number incre-
ments continuously.
Entry number Entry identification of buffer entries. This identification displays the
sequence of buffer entries
Indication number Number of the indication that occurred in the device. This number
increments continuously and is necessary for an analysis by
Siemens.
Indication Message text
Function Structure Path of the signal with the signal name
Name Signal name
Value Current state of the command. Also pay attention to the value
quality to check whether the value is up to date.
Quality The quality of the value shows the source of the value and whether
the value is up to date.
Cause Additional information such as the cause and validity
Number DIGSI address of the signal
Motor startup time Time of motor starting
Starting current Current needed by the motor to start up
Starting voltage Voltage needed by the motor to start up
Start duration Time needed by the motor to start up
Logs
General
Indications are saved in logs inside the device and are available for later analyses. Different logs allow catego-
rization of indication logging based on operating states (for example, operational and fault logs) and based on
fields of application.
Table 3-4
Log Overview
Log Logging
Operational log Operational indications
Fault log Fault indications
Ground-fault log Ground-fault indications
3.1.5
3.1.5.1
System Functions
3.1 Indications
SIPROTEC 5, High-Voltage Bay Controller, Manual 53
C53000-G5040-C015-9, Edition 11.2017