Addr. Parameter C Setting Options Default Setting
_:102 Swi. seq. #:Check double
activat. blk.
•
no
•
yes
yes
_:103 Swi. seq. #:Time-out
monitoring
•
0
•
1
true
_:104 Swi. seq. #:Monitoring
time
0.02 s to 3600.00 s 30.00 s
_:105 Swi. seq. #:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
SBO w. normal
secur.
_:106 Swi. seq. #:SBO time-out 0.01 s to 1800.00 s 30.00 s
Switching authority
_:151 Swi. seq. #:Swi.dev.
related sw.auth.
•
0
•
1
false
_:152 Swi. seq. #:Specific sw.
authorities
•
0
•
1
true
_:115 Swi. seq. #:Specific
sw.auth. valid for
•
station
•
station/remote
•
remote
station/remote
_:153 Swi. seq. #:Num. of
specific sw.auth.
2 to 5 2
_:154 Swi. seq. #:Multiple
specific sw.auth.
•
0
•
1
false
Information List
No.
Information Data Class
(Type)
Type
Swi. seq. #
_:501 Swi. seq. #:>Enable start SPS I
_:502 Swi. seq. #:>Enable start (fixed) SPS I
_:503 Swi. seq. #:>Start SPS I
_:504 Swi. seq. #:>Cancel SPS I
_:505 Swi. seq. #:>Successful SPS I
_:506 Swi. seq. #:>Failed SPS I
_:53 Swi. seq. #:Health ENS O
_:302 Swi. seq. #:Execution ENS O
_:304 Swi. seq. #:Start SPC C
_:305 Swi. seq. #:Cancel SPC C
6.5.5
Control Functions
6.5 Switching Sequences
SIPROTEC 5, High-Voltage Bay Controller, Manual 431
C53000-G5040-C015-9, Edition 11.2017