Addr. Parameter C Setting Options Default Setting
_:117 49 Th.overl. #:Minimal
temperature
-55°C to 40°C -20°C
_:44 49 Th.overl. #:Tempera-
ture sensor
Setting options depend on
configuration
Information List
No. Information Data Class
(Type)
Type
49 Th.overl. #
_:500 49 Th.overl. #:>Block stage SPS I
_:501 49 Th.overl. #:>Reset thermal replica SPS I
_:54 49 Th.overl. #:Inactive SPS O
_:52 49 Th.overl. #:Behavior ENS O
_:53 49 Th.overl. #:Health ENS O
_:301 49 Th.overl. #:Current warning SPS O
_:302 49 Th.overl. #:Thermal warning SPS O
_:303 49 Th.overl. #:Block close SPS O
_:55 49 Th.overl. #:Pickup ACD O
_:300 49 Th.overl. #:Operate alarm only ACT O
_:57 49 Th.overl. #:Operate ACT O
_:304 49 Th.overl. #:Time until close MV O
_:305 49 Th.overl. #:Time until trip MV O
_:306 49 Th.overl. #:Overload MV O
_:310 49 Th.overl. #:Equival. current MV O
7.27.6
Protection and Automation Functions
7.27 Thermal Overload Protection, 1-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual 901
C53000-G5040-C015-9, Edition 11.2017