Addr. Parameter C Setting Options Default Setting
_:105 Circuit break.:Indicat. of
breaking values
with trip
always
always
Information List
No. Information Data Class
(Type)
Type
Circuit break.
_:500 Circuit break.:>Ready SPS I
_:501 Circuit break.:>Acquisition blocking SPS I
_:502 Circuit break.:>Reset switch statist. SPS I
_:504 Circuit break.:>Reset AcqBlk&Subst SPS I
_:503 Circuit break.:External health ENS I
_:53 Circuit break.:Health ENS O
_:58 Circuit break.:Position DPC C
_:300 Circuit break.:Trip/open cmd. SPS O
_:301 Circuit break.:Close command SPS O
_:302 Circuit break.:Command active SPS O
_:303 Circuit break.:Definitive trip SPS O
_:304 Circuit break.:Alarm suppression SPS O
_:306 Circuit break.:Op.ct. INS O
_:307 Circuit break.:ΣI Brk. BCR O
_:308 Circuit break.:ΣIA Brk. BCR O
_:309 Circuit break.:ΣIB Brk. BCR O
_:310 Circuit break.:ΣIC Brk. BCR O
_:311 Circuit break.:Break.-current phs A MV O
_:312 Circuit break.:Break.-current phs B MV O
_:313 Circuit break.:Break.-current phs C MV O
_:317 Circuit break.:Break. current 3I0/IN MV O
_:314 Circuit break.:Break. voltage phs A MV O
_:315 Circuit break.:Break. voltage phs B MV O
_:316 Circuit break.:Break. voltage phs C MV O
_:322 Circuit break.:CB open hours INS O
_:323 Circuit break.:Operating hours INS O
Circuit-Breaker Position Recognition for Protection-Related Auxiliary
Functions
Overview
This function block calculates the position of the circuit breaker from the evaluation of the auxiliary contacts
and the current flow.
This information is needed in the following protection-related additional functions:
Trip logic (see )
Detection of manual closing (see 5.5.9.1 Function Description)
Process monitor (see )
Its use is described in the respective chapters.
The control does not use this information. The control evaluates the circuit-breaker auxiliary contacts.