Addr. Parameter C Setting Options Default Setting
_:4891:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:105 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:4891:33 Inverse-T 1:Effect. b.
cold-load pickup
no
yes
no
_:4891:40 Inverse-T 1:Stage
blocked
no
yes
no
_:4891:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:106 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: bin.input
_:4891:34 Inverse-T 1:Effected by
binary input
no
yes
no
_:4891:41 Inverse-T 1:Stage
blocked
no
yes
no
_:4891:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:107 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Information List
No.
Information Data Class
(Type)
Type
Inverse-T 1
_:4891:81 Inverse-T 1:>Block stage SPS I
_:4891:501 Inverse-T 1:>Release delay & op. SPS I
_:4891:84 Inverse-T 1:>Activ. dyn. settings SPS I
_:4891:500 Inverse-T 1:>Block delay & op. SPS I
_:4891:54 Inverse-T 1:Inactive SPS O
_:4891:52 Inverse-T 1:Behavior ENS O
_:4891:53 Inverse-T 1:Health ENS O
_:4891:60 Inverse-T 1:Inrush blocks operate SPS O
_:4891:62 Inverse-T 1:Dyn.set. AR cycle1act. SPS O
_:4891:63 Inverse-T 1:Dyn.set. AR cycle2act. SPS O
_:4891:64 Inverse-T 1:Dyn.set. AR cycle3act. SPS O
_:4891:65 Inverse-T 1:Dyn.set. ARcycl.>3act SPS O
7.7.6.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
728 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017