Addr. Parameter C Setting Options Default Setting
Dyn.s: AR off/n.rdy
_:4891:28 Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:4891:35 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:4891:29 Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:4891:36 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:4891:30 Inverse-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:4891:37 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:4891:31 Inverse-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:4891:38 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:4891:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:4891:32 Inverse-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:4891:39 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 727
C53000-G5040-C015-9, Edition 11.2017