Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.
NOTE
The value pairs must be entered in continuous order.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode
•
off
•
on
•
test
off
_:2 User curve #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:110 User curve #:Directional
mode
•
forward
•
reverse
forward
_:8 User curve #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:112 User curve #:Non-direc-
tional pickup
•
no
•
at volt.< & mem.empty
at volt.< &
mem.empty
_:109 User curve #:Directional
comparison
•
no
•
yes
no
_:111 User curve #:Release via
input signal
•
no
•
yes
no
_:10 User curve #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:26 User curve #:Dynamic
settings
•
no
•
yes
no
_:27 User curve #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:115 User curve #:Reset
•
instantaneous
•
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by
AR off/n.ready
•
no
•
yes
no
_:35 User curve #:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by
AR cycle 1
•
no
•
yes
no
_:36 User curve #:Stage
blocked
•
no
•
yes
no
7.6.6.3
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual 691
C53000-G5040-C015-9, Edition 11.2017