Set the time value in seconds. The characteristic curve is displaced using the Time dial parameter.
i
i
NOTE
The value pairs must be entered in continuous order.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode
off
on
test
off
_:2 User curve #:Operate &
flt.rec. blocked
no
yes
no
_:110 User curve #:Directional
mode
forward
reverse
forward
_:8 User curve #:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:112 User curve #:Non-direc-
tional pickup
no
at volt.< & mem.empty
at volt.< &
mem.empty
_:109 User curve #:Directional
comparison
no
yes
no
_:111 User curve #:Release via
input signal
no
yes
no
_:10 User curve #:Blk. by
meas.-volt. failure
no
yes
yes
_:26 User curve #:Dynamic
settings
no
yes
no
_:27 User curve #:Blk. w.
inrush curr. detect.
no
yes
no
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:115 User curve #:Reset
instantaneous
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by
AR off/n.ready
no
yes
no
_:35 User curve #:Stage
blocked
no
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by
AR cycle 1
no
yes
no
_:36 User curve #:Stage
blocked
no
yes
no
7.6.6.3
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual 691