This parameter is used to set the frequency difference for switching over between synchronous and asynchro-
nous operation.
Siemens recommends using the default setting of 0.01 Hz.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:5041:1 Sychr./Asycr.1:Mode
•
off
•
on
•
test
off
_:5041:101 Sychr./Asycr.1:Min. oper-
ating limit Vmin
0.300 V to 340.000 V 90.000 V
_:5041:102 Sychr./Asycr.1:Max.
operat. limit Vmax
0.300 V to 340.000 V 110.000 V
_:5041:110 Sychr./Asycr.
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞ 30.00 s
_:5041:108 Sychr./Asycr.1:Direct
close command
•
no
•
yes
no
_:5041:126 Sychr./Asycr.1:Voltage
adjustment
0.500 to 2.000 1.000
De-en.gized switch.
_:5041:105 Sychr./Asycr.1:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:5041:106 Sychr./Asycr.1:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:5041:107 Sychr./Asycr.1:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:5041:103 Sychr./Asycr.1:V1, V2
without voltage
0.300 V to 170.000 V 5.000 V
_:5041:104 Sychr./Asycr.1:V1, V2
with voltage
0.300 V to 340.000 V 80.000 V
_:5041:109 Sychr./Asycr.1:Supervi-
sion time
0.00 s to 60.00 s 0.10 s
Asynchr. op.mode
_:5041:114 Sychr./Asycr.1:Async.
operating mode
•
off
•
on
on
_:5041:113 Sychr./Asycr.1:CB make
time
0.01 s to 0.60 s 0.06 s
_:5041:115 Sychr./Asycr.1:Max.
voltage diff. V2>V1
0.000 V to 170.000 V 5.000 V
_:5041:116 Sychr./Asycr.1:Max.
voltage diff. V2<V1
0.000 V to 170.000 V 5.000 V
_:5041:117 Sychr./Asycr.1:Max.
frequency diff. f2>f1
0.000 Hz to 4.000 Hz 0.100 Hz
_:5041:118 Sychr./Asycr.1:Max.
frequency diff. f2<f1
0.000 Hz to 4.000 Hz 0.100 Hz
Synchr. op.mode
_:5041:119 Sychr./Asycr.1:Sync.
operating mode
•
off
•
on
on
_:5041:120 Sychr./Asycr.1:f-
threshold ASYN<->SYN
0.010 Hz to 0.200 Hz 0.010 Hz
6.4.8.3
Control Functions
6.4 Synchronization Function
386 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017