EasyManua.ls Logo

Siemens 6MD86 - Overvoltage Protection with Positive-Sequence Voltage; Overview of Functions; Structure of the Function

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overvoltage Protection with Positive-Sequence Voltage
Overview of Functions
The function Overvoltage protection with positive-sequence voltage (ANSI 59) is used to:
Detect symmetric stationary overvoltages
Supervise the voltage range if the positive-sequence voltage is the decisive quantity
Unbalanced overvoltages, for example, caused by ground faults and unbalanced faults, are not detected due
to the evaluation of the positive-sequence voltage.
Structure of the Function
The Overvoltage protection with positive-sequence voltage function is used in protection function groups,
which are based on voltage measurement.
The function Overvoltage protection with positive-sequence voltage comes factory-set with 2 stages. A
maximum of 3 tripping stages can be operated simultaneously in the function. The tripping stages have an
identical structure.
[dwovpu1s-030211-01.tif, 1, en_US]
Figure 7-144 Structure/Embedding of the Function
7.14
7.14.1
7.14.2
Protection and Automation Functions
7.14 Overvoltage Protection with Positive-Sequence Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual 795
C53000-G5040-C015-9, Edition 11.2017

Table of Contents