Settings
Addr. Parameter C Setting Options Default Setting
General
_:1 Syn./Asy.bal.#:Mode
•
off
•
on
•
test
off
_:101 Syn./Asy.bal.#:Min. oper-
ating limit Vmin
0.300 V to 340.000 V 90.000 V
_:102 Syn./Asy.bal.#:Max.
operat. limit Vmax
0.300 V to 340.000 V 110.000 V
_:110 Syn./
Asy.bal.#:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞ 30.00 s
_:108 Syn./Asy.bal.#:Direct
close command
•
no
•
yes
no
_:126 Syn./Asy.bal.#:Voltage
adjustment
0.500 to 2.000 1.000
De-en.gized switch.
_:105 Syn./Asy.bal.#:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:106 Syn./Asy.bal.#:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:107 Syn./Asy.bal.#:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:103 Syn./Asy.bal.#:V1, V2
without voltage
0.300 V to 170.000 V 5.000 V
_:104 Syn./Asy.bal.#:V1, V2
with voltage
0.300 V to 340.000 V 80.000 V
_:109 Syn./Asy.bal.#:Supervi-
sion time
0.00 s to 60.00 s 0.10 s
Asynchr. op.mode
_:114 Syn./Asy.bal.#:Async.
operating mode
•
off
•
on
off
_:113 Syn./Asy.bal.#:CB make
time
0.01 s to 0.60 s 0.06 s
_:115 Syn./Asy.bal.#:Max.
voltage diff. V2>V1
0.000 V to 170.000 V 2.000 V
_:116 Syn./Asy.bal.#:Max.
voltage diff. V2<V1
0.000 V to 170.000 V 2.000 V
_:117 Syn./Asy.bal.#:Max.
frequency diff. f2>f1
0.000 Hz to 4.000 Hz 0.100 Hz
_:118 Syn./Asy.bal.#:Max.
frequency diff. f2<f1
0.000 Hz to 4.000 Hz 0.100 Hz
Synchr. op.mode
_:119 Syn./Asy.bal.#:Sync.
operating mode
•
off
•
on
off
_:120 Syn./Asy.bal.#:f-
threshold ASYN<->SYN
0.010 Hz to 0.200 Hz 0.010 Hz
_:122 Syn./Asy.bal.#:Max.
voltage diff. V2>V1
0.000 V to 170.000 V 2.000 V
_:123 Syn./Asy.bal.#:Max.
voltage diff. V2<V1
0.000 V to 170.000 V 2.000 V
6.4.14.3
Control Functions
6.4 Synchronization Function
418 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017