EasyManua.ls Logo

Siemens 6MD86 - Cold-Load Pickup Detection (Optional)

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cold-Load Pickup Detection (Optional)
Logic
[loprocls-180912-01.tif, 1, en_US]
Figure 5-98
Logic Diagram of the Cold-Load Pickup Detection Function Block
The Cold-load pickup detection function block detects that a specific time has been exceeded after deactiva-
tion of the line or protected object. If you want to connect the protected object again, you must note that an
increased load-current requirement exists for a limited time after connection. This results from the nature of
the load.
The Cold-load pickup detection function block ensures that different parameters are used for an adjustable
time after connection. For example, for the time of the Min. CB-open time parameter, you can increase
the threshold value of a protection function or you can select a special characteristic curve.
If the Cold-load pickup detection function block detects an open feeder and the set time of the Min. CB-
open time parameter has expired, the indication >Activate cold-load is generated.
With the >Activate cold-load indication, you can activate a parameter set of the Cold-load pickup func-
tion. Via the binary input signal >Activate cold-load, you can also activate the >Activate cold-load
indication directly.
If the Cold-load pickup detection function block detects closure and the corresponding load current, it starts
the time set in the Dropout delay CB closed parameter. The >Activate cold-load indication and
the activated parameter set are deactivated after this time has elapsed.
5.8.9
Function-Group Types
5.8 Process Monitor
SIPROTEC 5, High-Voltage Bay Controller, Manual 297
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals