Parameter: Scaling COMTRADE
•
Recommended setting value Scaling COMTRADE = Secondary values
With the Scaling COMTRADE parameter, you scale the fault record data for the COMTRADE format. Possible
setting values are Primary values or Secondary values.
Settings
Addr. Parameter C Setting Options Default Setting
General
_:2731:1 General:Mode
•
on
•
test
on
Control
_:2761:130 Control:Fault recording
•
with pickup
•
with pickup & AR cyc.
•
user-defined
with pickup
_:2761:131 Control:Storage
•
always
•
with trip
always
_:2761:111 Control:Maximum record
time
0.20 s to 20.00 s 5.00 s
_:2761:112 Control:Pre-trigger time 0.05 s to 4.00 s 0.50 s
_:2761:113 Control:Post-trigger time 0.05 s to 0.50 s 0.50 s
_:2761:116 Control:Manual record time 0.20 s to 20.00 s 0.50 s
_:2761:140 Control:Sampling
frequency
•
8 kHz
•
4 kHz
•
2 kHz
•
1 kHz
2 kHz
Information List
No.
Information Data Class
(Type)
Type
Binary IO
_:2731:51 General:Mode (controllable) ENC C
_:2731:52 General:Behavior ENS O
_:2731:53 General:Health ENS O
Binary IO
_:2761:300 Control:Start record SPC C
_:2761:305 Control:Reset memory SPC C
_:2761:306 Control:Clear memory SPC C
_:2761:502 Control:>External start SPS I
_:2761:503 Control:>Manual start SPS I
_:2761:310 Control:Fault number INS O
_:2761:311 Control:Recording started SPS O
_:2761:314 Control:Record made SPS O
_:2761:327 Control:Tmax reduced SPS O
3.4.5
3.4.6
System Functions
3.4 Fault Recording
96 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017