Siemens 6MD86 - Cycle Control with Operating Mode 3: with Tripping;Without Action Time

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[loanrwir-140611-01.tif, 1, en_US]
Figure 7-36
Cycle Control with Operating Mode: With Pickup/With Action Time
Cycle Control with Operating Mode 3: With Tripping/Without Action Time
The cycle control checks the availability for each automatic reclosing cycle. In Figure 7-37, the cycle control for
the 1st automatic reclosing cycle and other reclosing cycles is illustrated. The further automatic reclosing
cycles are generally described with the cycle number n and apply for all other configured automatic reclosing
cycles.
The cycle availability is influenced through the parameterization of the dead time and through a binary input.
In this way, setting the parameter Dead time aft. 3-pole trip to invalid avoids an automatic
reclosing after 3-pole tripping. Correspondingly, there is no automatic reclosing function after 1-pole tripping
if the Dead time aft. 1-pole trip
24
to invalid. If both dead times are set to invalid, the respec-
7.2.4.8
24
is not available for devices with only 3-pole tripping
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual 557
C53000-G5040-C015-9, Edition 11.2017