Addr. Parameter C Setting Options Default Setting
_:32:3 Stage 2:Threshold 40.00 Hz to 70.00 Hz 1.00 Hz
_:32:6 Stage 2:Operate delay 0.00 s to 600.00 s 5.00 s
Information List
No. Information Data Class
(Type)
Type
General
_:2311:300 General:Undervoltage blocking SPS O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:31:81 Stage 1:>Block stage SPS I
_:31:54 Stage 1:Inactive SPS O
_:31:52 Stage 1:Behavior ENS O
_:31:53 Stage 1:Health ENS O
_:31:55 Stage 1:Pickup ACD O
_:31:56 Stage 1:Operate delay expired ACT O
_:31:57 Stage 1:Operate ACT O
Stage 2
_:32:81 Stage 2:>Block stage SPS I
_:32:54 Stage 2:Inactive SPS O
_:32:52 Stage 2:Behavior ENS O
_:32:53 Stage 2:Health ENS O
_:32:55 Stage 2:Pickup ACD O
_:32:56 Stage 2:Operate delay expired ACT O
_:32:57 Stage 2:Operate ACT O
7.18.6
Protection and Automation Functions
7.18 Overfrequency Protection
828 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017